This site is in beta — data may be incomplete and features are still being added.
Council Meeting/Documents/Relevant Official Community Plan Policies (Attachment 4)
Appendix

Relevant Official Community Plan Policies (Attachment 4)

February 6, 2024Pages 169–1732 sections

Excerpts from the Official Community Plan Bylaw No. 811, 2011 relevant to the development application.

1 CALL TO ORDER- Councillor Rogers, Acting Chair, called the meeting to order at 7:03 p.m.
Policy LU1.5 Mixed Residential designationPolicy HS1.1 Range of Housing Types

20-Unit Townhouse Development, View Royal_Updated

HCM 6th TWSC 2: Eltham Rd & Access A1

Timing Plan: PD-Opening-AM

Intersection
Int Delay, s/veh 1.8
Movement EBL EBT WBT WBR SBL SBR
Lane Configurations
Traffic Vol, veh/h 3 14 22 0 0 7
Future Vol, veh/h 3 14 22 0 0 7
Conflicting Peds, #/hr 0 0 0 0 0 0
Sign Control Free Free Free Free Stop Stop
RT Channelized - None - None - None
Storage Length - - - - 0 -
Veh in Median Storage, # - 0 0 - 0 -
Grade, % - 0 0 - 0 -
Peak Hour Factor 92 92 92 92 92 92
Heavy Vehicles, % 2 2 2 2 2 2
Mvmt Flow 3 15 24 0 0 8
Major/Minor Major1 Major2 Minor2
Conflicting Flow All 24 0 - 0 45 24
Stage 1 - - - - 24 -
Stage 2 - - - - 21 -
Critical Hdwy 4.12 - - - 6.42 6.22
Critical Hdwy Stg 1 - - - - 5.42 -
Critical Hdwy Stg 2 - - - - 5.42 -
Follow-up Hdwy 2.218 - - - 3.518 3.318
Pot Cap-1 Maneuver 1591 - - - 965 1052
Stage 1 - - - - 999 -
Stage 2 - - - - 1002 -
Platoon blocked, % - - - -
Mov Cap-1 Maneuver 1591 - - - 963 1052
Mov Cap-2 Maneuver - - - - 963 -
Stage 1 - - - - 997 -
Stage 2 - - - - 1002 -
Approach EB WB SB
HCM Control Delay, s 1.3 0 8.4
HCM LOS A
Minor Lane/Major Mvmt EBL EBT WBT WBR SBLn1
Capacity (veh/h) 1591 - - - 1052
HCM Lane V/C Ratio 0.002 - - - 0.007
HCM Control Delay (s) 7.3 0 - - 8.4
HCM Lane LOS A A - - A
HCM 95th %tile Q(veh) 0 - - - 0

Post Development AM Peak Hour, Updated Addoz Engineering Inc. Synchro 10 Report 08-22-2023


HCM 6th TWSC 1: Helmcken Rd & Eltham Rd

Timing Plan: PD-Opening-PM

Intersection
Int Delay, s/veh 0.9
Movement WBL WBR NBT NBR SBL SBT
Lane Configurations
Traffic Vol, veh/h 11 18 244 16 17 225
Future Vol, veh/h 11 18 244 16 17 225
Conflicting Peds, #/hr 16 16 0 16 16 0
Sign Control Stop Stop Free Free Free Free
RT Channelized - None - None - None
Storage Length 0 - - - - -
Veh in Median Storage, # 0 - 0 - - 0
Grade, % 0 - 0 - - 0
Peak Hour Factor 94 94 94 94 94 94
Heavy Vehicles, % 2 2 3 3 3 3
Mvmt Flow 12 19 260 17 18 239
Major/Minor Minor1 Major1 Major2
Conflicting Flow All 576 301 0 0 293 0
Stage 1 285 - - - - -
Stage 2 291 - - - - -
Critical Hdwy 6.42 6.22 - - 4.13 -
Critical Hdwy Stg 1 5.42 - - - - -
Critical Hdwy Stg 2 5.42 - - - - -
Follow-up Hdwy 3.518 3.318 - - 2.227 -
Pot Cap-1 Maneuver 479 739 - - 1263 -
Stage 1 763 - - - - -
Stage 2 759 - - - - -
Platoon blocked, % - - -
Mov Cap-1 Maneuver 458 719 - - 1246 -
Mov Cap-2 Maneuver 458 - - - - -
Stage 1 752 - - - - -
Stage 2 736 - - - - -
Approach WB NB SB
HCM Control Delay, s 11.4 0 0.6
HCM LOS B
Minor Lane/Major Mvmt NBT NBR WBLn1 SBL SBT
Capacity (veh/h) - - 591 1246 -
HCM Lane V/C Ratio - - 0.052 0.015 -
HCM Control Delay (s) - - 11.4 7.9 0
HCM Lane LOS - - B A A
HCM 95th %tile Q(veh) - - 0.2 0 -

Post Development PM Peak Hour, Updated Addoz Engineering Inc. Synchro 10 Report 08-22-2023


HCM 6th TWSC 2: Eltham Rd & Access A1

Timing Plan: PD-Opening-PM

Intersection
Int Delay, s/veh 1.4
Movement EBL EBT WBT WBR SBL SBR
Lane Configurations
Traffic Vol, veh/h 6 27 24 1 0 5
Future Vol, veh/h 6 27 24 1 0 5
Conflicting Peds, #/hr 0 0 0 0 0 0
Sign Control Free Free Free Free Stop Stop
RT Channelized - None - None - None
Storage Length - - - - 0 -
Veh in Median Storage, # - 0 0 - 0 -
Grade, % - 0 0 - 0 -
Peak Hour Factor 92 92 92 92 92 92
Heavy Vehicles, % 2 2 2 2 2 2
Mvmt Flow 7 29 26 1 0 5
Major/Minor Major1 Major2 Minor2
Conflicting Flow All 27 0 - 0 70 27
Stage 1 - - - - 27 -
Stage 2 - - - - 43 -
Critical Hdwy 4.12 - - - 6.42 6.22
Critical Hdwy Stg 1 - - - - 5.42 -
Critical Hdwy Stg 2 - - - - 5.42 -
Follow-up Hdwy 2.218 - - - 3.518 3.318
Pot Cap-1 Maneuver 1587 - - - 934 1048
Stage 1 - - - - 996 -
Stage 2 - - - - 979 -
Platoon blocked, % - - - -
Mov Cap-1 Maneuver 1587 - - - 930 1048
Mov Cap-2 Maneuver - - - - 930 -
Stage 1 - - - - 992 -
Stage 2 - - - - 979 -
Approach EB WB SB
HCM Control Delay, s 1.3 0 8.5
HCM LOS A
Minor Lane/Major Mvmt EBL EBT WBT WBR SBLn1
Capacity (veh/h) 1587 - - - 1048
HCM Lane V/C Ratio 0.004 - - - 0.005
HCM Control Delay (s) 7.3 0 - - 8.5
HCM Lane LOS A A - - A
HCM 95th %tile Q(veh) 0 - - - 0

Post Development PM Peak Hour, Updated Addoz Engineering Inc. Synchro 10 Report 08-22-2023


Page 169–173

J.E. ANDERSON & ASSOCIATES

SURVEYORS - ENGINEERS

November 24, 2023

JEA File No. 33862 View Royal File No. REZ 2023-04 Royale Ventures Corp

REVIEWED By ileung at 4:07 pm, Dec 07, 2023 File: ENG2022-06 Conditions:

  1. Reviewed for rezoning only
  2. Detail Design SWMP required prior to building permit. Stormwater storage volumes and detail design to be confirmed as part of servicing agreement
  3. S219 Covenant on title required for maintenance of stormwater management structures, to be completed as a condition of building permit
  4. Water servicing requirements deferred to CRD for comment

Re: Pebbles - Proposed Development at 294 & 296 Eltham Rd & 242 Helmcken Rd Sewer, Water and Storm Drain Servicing Review

1.0 Introduction

JE Anderson and Associates has been retained as the civil consultant for the proposed multi-family development which consists of 20 town houses. The following design brief will review the post-development impact to The Town of View Royal’s sanitary and storm drainage systems as well as the CRD water distribution system.

2.0 Design Criteria Applied/Assumptions Made

The following assumptions and design guidelines have been used in this review.

Sewer loads:

  • 2.8 capita per unit
  • Average daily sewage flows = 240 L/cap/day
  • Harmon formula for Peaking Factor
  • Inflow and Infiltration rate of 0.12 L/ha/s

Water demands:

  • 2.8 capita per unit for each townhouse dwelling
  • Average daily demand of 545 L/cap/day (as per CRD design guidelines)
  • Fire flow demand as per Fire Underwriter Survey and CRD minimums

Drainage calculations:

  • Rational Method for pre and post development flow
  • SCS Method through HydroCAD for post-development flow
  • 2022 Victoria Gonzales IDF Curve
  • Pre-development Tc = 10 min and combined runoff coefficient based on c = 0.35 for pervious and c = 0.9 for impervious areas
  • Post-development Tc = 10 min due to routing through SWM systems
  • SWM system will release at the pre-development 10-year flowrates.
  • 10% climate change factor added to 10-year post development flows

3.0 Calculations

3.1 Sewer

The calculations enclosed in Appendix A indicate that the post-development peak wet-weather flow (PWWF) is 0.70 L/s.

3.2 Water

The calculations enclosed in Appendix B indicate that the post-development average daily demand (ADD) is 30 520 L/day (0.35 L/s).

Preliminary Fire Underwriters Survey calculations indicate the required fire flow for the development is 4,000 L/min. CRD requires a minimum fire flow of 4,800 L/min.

3.3 Storm Drainage

The calculations enclosed in Appendix C indicate that the pre-development 10-yr storm flow is 6 L/s and post-development flow is 15 L/s.

The proposed on-site stormwater management (SWM) system will reduce the post-development flow to the permitted release rate of the pre-development 10-yr storm event.

3.4 Stormwater Management

The proposed stormwater management systems are designed to release the post-development flow at the 10-yr pre-development flow rates. The stormwater management calculations include a 10% climate change factor for the 10-yr post-development. Each catch basin within the proposed roadway will enter a Type 1 oil and grit separator to treat the runoff before entering the storm main and stormwater management systems.

The required storage volume is 24.7 cubic meters. The stormwater will be stored via storage chamber, and will be fully designed at the building permit stage of this development.

A stormwater operations and maintenance covenant will be required to be registered on title.

6.0 Downstream Impacts

Sewer – The proposed flow is 0.53 L/s. The downstream sanitary system is a 150mm PVC sewer main @ 1.6% which has a capacity of approximately 19.3 L/s. The proposed development meets the allowable FSR from the Sewer Master Plan and will use 2.75% of the downstream 150mm PVC during a full-flow event.

A review of the Town of View Royal Sewer Master Plan – Draft (2017) indicates that the proposed development is consistent with the report’s assumptions for FSR and there are no identified capacity issues downstream.

Water – From the given hydrant curve for VRF061 at Helmcken & Eltham, we determined the Hydraulic Grade Line for the site is approximately 116 m under max day demand. The resultant head for the existing hydrant is sufficient in meeting the FUS flow of 4,000 L/min with a remaining head of 133.6 m.

Pebbles – Design Brief Memo J.E. ANDERSON & ASSOCIATES

Page 169–173
Extracted from: 2024 02 06 Council Agenda - Agenda - Pdf