Appendix
Block A Elevations (Left/Right)
May 19, 2020Page 2551 section
Block A: Elevations
Customer: Limona Holdings Ltd. Address: TLC Subdivision Drawing Name: Block A: Elevations Issue Date: April 03, 2020 Drawn By: S.T. Checked By: Kyle Leggett Drawing Scale: 1/4" = 1'-0" Sheet Number: A6
Left Elevation
Scale: 1/4" = 1' - 0"
Data Summary:
- Exposing Building Face: 66.30m²
- Limiting Distance: 1.55m
- Area of Glazed Openings: 1.74m²
- % Glazed Openings: 2.62%
- 45 min Fire-Resistance Rating: not required
- Type of Cladding: no limits
- Permitted % of Glazed Openings (as per Table 9.10.15.4): 8.51%
- Permitted Aggregate Area of Glazed Openings: 5.64m²
Right Elevation
Scale: 1/4" = 1' - 0"
Data Summary:
- Exposing Building Face: 66.30m²
- Limiting Distance: 13.84m
- Area of Glazed Openings: 3.80m²
- % Glazed Openings: 5.73%
- 45 min Fire-Resistance Rating: not required
- Type of Cladding: no limits
- Permitted % of Glazed Openings (as per Table 9.10.15.4): -
- Permitted Aggregate Area of Glazed Openings: -
Exterior Finishes Schedule
| Key | Finish | Description |
|---|---|---|
| A | ROOFING: | ASPHALT ROOFING WITH RAISED RIDGE & HIP CAPS |
| B | GUTTER & SOFFIT: | ALUMINUM GUTTER AND NON-VENTED SOFFIT |
| C | BARGE BOARD: | 2x10 WITH 1x4 DOUBLE BARGE BOARD, PAINTED TRIM COLOUR |
| D | WINDOW & DOOR TRIM: | 1x4 TRIM BOARDS - PAINTED/STAINED |
| E | CORNER TRIM: | 1x4 CORNER BOARDS - PAINTED/STAINED |
| F1 | WALL FINISH: | HARDIE-PLANK SIDING LAPPED TO 4" EXPOSURE - COLOUR AS PER OWNERS SPECS |
| F2 | WALL FINISH: | HARDIE-BOARD AND BATTEN CHECKER PATTERN - COLOUR AS PER OWNERS SPECS |
| F3 | WALL FINISH: | HARDIE-PLANK SIDING LAPPED TO 4" EXPOSURE - COLOUR AS PER OWNERS SPECS |
| G | BELLY BAND: | 2x12 PAINTED BELLY BAND WITH FLASHING, PAINTED TRIM COLOUR |
Notes
- ALL WINDOWS MUST COMPLY WITH BCSC AND NAFS REQUIREMENTS
- MUST BE CLEARLY LABELED ON ALL WINDOW UNITS UPON INSTALLATION FOR INSPECTION.
- ONE EXTERIOR DOOR IS PERMITTED TO HAVE A HIGHER U-VALUE OF 2.6, ALL OTHERS MUST BE LOWER.
- GARAGE VEHICULAR DOORS MUST BE MINIMUM NOMINAL RSI OF 1.1
Page 255