Calculations of required fire-flow based on the 2020 Fire Underwriters Survey for the North and East buildings of the development.

2. APPROVAL OF AGENDA (motion to approve)
East Building fire-flow required = 223.1 L/s (13387.5 L/min)North Building fire-flow required = 201.9 L/s (12112.5 L/min)Construction Type IV-C

APPENDIX D

FIRE FLOW ESTIMATES AND HYDRANT CURVE DATA

Underground Utilities Brief | Prepared for Boardwalk REIT 339 / 341 / 345 Island Highway, View Royal, BC

Page 137–139

Fire Flow Calculation - based on 2020 Fire Underwriters Survey

McElhanney Proj.# 2241-22-149 #339 Island Highway - East Building (East Section)

Construction Coefficient (C)

C= Construction Type
1.5 for Type V Wood Frame Construction
0.8 for Type IV-A Mass Timber Construction
0.9 for Type IV-B Mass Timber Construction
1.0 for Type IV-C Mass Timber Construction
1.5 for Type IV-D Mass Timber Construction
1.0 for Type III Ordinary Construction (Joisted Masonry)
0.8 for Type II Noncombustible Construction
0.6 for Type I Fire Resistive Construction

C = 1.5 Type IV-C

Total Effective Floor Area (A)

A = 4100 sq.m 44035 sq.ft = 4091 sq.m

Required Fire Flow (RFF)

F = 220C(A^1/2) F = 21130 L/min F = 21000 L/min (Rounded to nearest 1000) F = 350.0 L/s

Occupancy and Contents Adjustment Factor

% Content Description
-25 Noncombustible Contents
-15 Limited Combustible Contents
0 Combustible Contents
15 Free Burning Contents
25 Rapid Burning Contents

%= -15 Residential Occupancies, Limited (Description of Major Occupancy and Contents)

Amount of Fire-Flow reduction (Occupancy): F = -52.5 L/s Estimated Reduced Fire-Flow (Occupancy): F = 297.5 L/s

Automatic Sprinkler Protection

Sprinkler Credits Automatic Sprinkler System Design
-30% design and installed to NFPA 13
-10% water supply stnd for system and FD Hoses
-10% Fully supervised system
-25% Community Level Automatic Sprinkler (see guide pg 28)

%= -50 Amount of Fire-Flow reduction (Sprinkler): F = -148.8 L/s

Exposure Adjustment Charge

# of sides Separation Charge % Notes
1 0 - 3 m 25 North to Building L Firewall (0m)
0 3.1 - 10 m 0
0 10.1 - 20 m 0
0 20.1 - 30 m 0
3 > 30 m 0 East to Ex. Firehall (34m), South to Prop Line (32m), West to South Building (22m [auto sprin])

Total # of sides: 4 Charge %: 25% (75% max) Exposure Separation charge: F = 74.4 L/s

See Table 6 for exposure adjustment charges for subject building considering construction type of expose building face

Estimated Fire-Flow (with reductions & charges)

F = 223.1 L/s

TOTAL FUS FIRE-FLOW COVERAGE REQUIRED:

F = 223.1 L/s 13387.5 L/min

2023-02-23 22-149 FUS 2/23/2023


Page 137–139

Fire Flow Calculation - based on 2020 Fire Underwriters Survey

McElhanney Proj.# 2241-22-149 #339 Island Highway - East Building (North Section)

Construction Coefficient (C)

C= Construction Type
1.5 for Type V Wood Frame Construction
0.8 for Type IV-A Mass Timber Construction
0.9 for Type IV-B Mass Timber Construction
1.0 for Type IV-C Mass Timber Construction
1.5 for Type IV-D Mass Timber Construction
1.0 for Type III Ordinary Construction (Joisted Masonry)
0.8 for Type II Noncombustible Construction
0.6 for Type I Fire Resistive Construction

C = 1.5 Type IV-C

Total Effective Floor Area (A)

A = 3400 sq.m 36297 sq.ft = 3372 sq.m

Required Fire Flow (RFF)

F = 220C(A^1/2) F = 19242 L/min F = 19000 L/min (Rounded to nearest 1000) F = 316.7 L/s

Occupancy and Contents Adjustment Factor

% Content Description
-25 Noncombustible Contents
-15 Limited Combustible Contents
0 Combustible Contents
15 Free Burning Contents
25 Rapid Burning Contents

%= -15 Residential Occupancies, Limited (Description of Major Occupancy and Contents)

Amount of Fire-Flow reduction (Occupancy): F = -47.5 L/s Estimated Reduced Fire-Flow (Occupancy): F = 269.2 L/s

Automatic Sprinkler Protection

Sprinkler Credits Automatic Sprinkler System Design
-30% design and installed to NFPA 13
-10% water supply stnd for system and FD Hoses
-10% Fully supervised system
-25% Community Level Automatic Sprinkler (see guide pg 28)

%= -50 Amount of Fire-Flow reduction (Sprinkler): F = -134.6 L/s

Exposure Adjustment Charge

# of sides Separation Charge % Notes
1 0 - 3 m 25 South to Building L Firewall (0m)
0 3.1 - 10 m 0
0 10.1 - 20 m 0
0 20.1 - 30 m 0
3 > 30 m 0 East to Firehall (34m), North to # IslHwy (44m), West to North Building (13m [auto sprinker])

Total # of sides: 4 Charge %: 25% (75% max) Exposure Separation charge: F = 67.3 L/s

See Table 6 for exposure adjustment charges for subject building considering construction type of expose building face

Estimated Fire-Flow (with reductions & charges)

F = 201.9 L/s

TOTAL FUS FIRE-FLOW COVERAGE REQUIRED:

F = 201.9 L/s 12112.5 L/min

2023-02-23 22-149 FUS 2/23/2023

Page 137–139